6.3. GDFI Fault
Before the inverter connects to the Grid, it will detect the impedance (effective resistance) of the
solar PV + to Ground, and the impedance of the solar PV - to ground. If any of the impedance
values are less than 33kΩ, the inverter will not connect to the Grid and will report an error F24
on its LCD.
7. MAINTENANCE
The inverter is low maintenance. However, it is important that at least twice a year (for dusty
environments this may need to be carried out weekly) all the cooling fans, air ducts are cleaned
and dust free.
Check if there are no fault codes and Lithium battery communication is correct.
Weekly cleaning statement: Suggest micromesh filters as an available option, micro ants here
are a real problem.
APPENDIX A
No.
RS485 Pin
1
485_B
2
485_A
3
GND_485
4
CAN_H1
5
CAN_L1
6
GND_485
7
485_A
8
485_B
Definition of RJ45 Port Pin for BMS1
Definition of RJ45 Port Pin for BMS2
No.
RS485 Pin
1
485_B
2
485_A
3
GND_485
4
CAN_H2
5
CAN_L2
6
GND_485
7
485_A
8
485_B
Содержание SUN-25K-SG01HP3-EU-BM2
Страница 19: ...Page 19 Hybrid Inverter Installer Manual 4 4 1 Function Ports Definition ...
Страница 26: ...Page 26 Hybrid Inverter Installer Manual ...
Страница 27: ...Page 27 Hybrid Inverter Installer Manual ...
Страница 29: ...Page 29 Hybrid Inverter Installer Manual 4 10 Wiring System for Inverter ...
Страница 30: ...Page 30 Hybrid Inverter Installer Manual 4 11 Wiring Diagram ...
Страница 31: ...Page 31 Hybrid Inverter Installer Manual ...
Страница 32: ...Page 32 Hybrid Inverter Installer Manual 4 12 Typical Application Diagram of Diesel Generator ...
Страница 33: ...Page 33 Hybrid Inverter Installer Manual 4 13 Three Phase Parallel Connection Diagram 01 02 03 ...
Страница 44: ...Page 44 Hybrid Inverter Installer Manual ...
Страница 68: ...Page 68 Hybrid Inverter Installer Manual 5 23 3 MODE III With Smart Load 5 23 4 MODE IV AC Couple ...