5-6
Sun StorEdge T3 and T3+ Array Field Service Manual • September 2001
Note –
A warning message will appear in the array
syslog
file if a disk drive
reaches 65 degrees C. The array automatically starts spinning down an individual
drive if the drive’s temperature reaches 75 degrees C.
5.2
Disk Drive LEDs
LEDs at the top of each disk drive indicate drive activity and status. These LEDs
appear in the front cover on the unit.
TABLE 5-2
lists the possible drive LED states
and a description for each state.
FIGURE 5-1
Disk Drive LEDs (Viewed Through Front Cover)
TABLE 5-2
Disk Drive LED Descriptions
Drive Activity
(Green)
Drive Status
(Amber)
Descriptions
Off
Off
Drive not installed (not recognized)
Slow blink
Off
Drive is spinning up or down
Solid
Off
Drive OK, idle
Disk drive LEDs
Содержание StorEdge T3+
Страница 5: ...Regulatory Compliance Statements v ...
Страница 14: ...xiv Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 36: ...1 6 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 70: ...3 24 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 86: ...4 16 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 154: ...8 30 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 164: ...9 10 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 188: ...10 24 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 222: ...D 4 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 228: ...F 4 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 240: ...Index 12 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...