7-10
Sun StorEdge T3 and T3+ Array Field Service Manual • September 2001
power and cooling unit that contains the battery must be replaced within forty-five
days of receiving the first warning message. The warning message indicates which
power and cooling unit needs to be replaced.
7.4.3
Removing and Replacing the UPS Battery
Note –
REVIEWERS—This is a cold-swap procedure.
7.4.3.1
Remove the UPS Battery
1. Remove the PCU from the array.
See “Removing and Replacing a Power and Cooling Unit” on page 4.
Caution –
Any power and cooling unit that is removed must be replaced within 30
minutes or the Sun StorEdge T3 and T3+ array and all attached arrays automatically
shut down and power off.
2. Turn the PCU over such that the bottom of the unit is facing up as shown in
FIGURE 7-4
.
FIGURE 7-4
Turning the PCU upside down
3. Remove the four Phillips screws from the panel on the bottom and side of the
PCU as shown in
FIGURE 7-5
.
Use care in removing the screws so they do not fall into the vent holes of the PCU.
Содержание StorEdge T3+
Страница 5: ...Regulatory Compliance Statements v ...
Страница 14: ...xiv Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 36: ...1 6 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 70: ...3 24 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 86: ...4 16 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 154: ...8 30 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 164: ...9 10 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 188: ...10 24 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 222: ...D 4 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 228: ...F 4 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...
Страница 240: ...Index 12 Sun StorEdge T3 and T3 Array Field Service Manual September 2001 ...