S-CB Px 120 Manual
62
Menu B: Hot water
B 5 L e g i o t e m p
8 5 ° C
Pasteurisation function of the boiler. This parameter is the
selected hot water temperature during the pasteurisation
function of the boiler.
Menu B: Hot water
B 6 L e g i o h y s t
2 ° C
Pasteurisation function of the boiler. This parameter is the
selected hysteresis during the pasteurisation function of the
boiler.
Menu B: Hot water
B 7 L e g i o h o l d
2 M i n
Pasteurisation function of the boiler. This parameter is the
selected time period for the pasteurisation function of the
boiler.
Menu B: Hot water
B 8 L e g i o i n t r
0
Pasteurisation function of the boiler. This parameter controls
if the CH demand can be interrupted by the pasteurisation
function of the boiler.
0 = Yes
1 = No
Menu B: Hot water
B 9 D H d s c O f f 2
4 ° C
Function for the direct hot water boiler.
This parameter is de off set of the selected HW temperature
of the boiler.
Menu B: Hot water
B A D H d s c P r b 2 3
2 0 ° C
Function for the direct hot water boiler.
This parameter is the proportional range of the selected HW
temperature of the boiler.
Menu B: Hot water
B B D H d s c D i f 2
1 0 ° C
Function for the direct hot water boiler.
This parameter is the hysteresis of the selected HW temper-
ature of the boiler.
Содержание S-CB Px 120
Страница 2: ...S CB Px 120 Manual 2 ...
Страница 6: ...S CB Px 120 Manual 6 ...
Страница 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Страница 34: ...S CB Px 120 Manual 34 ...
Страница 111: ...S CB Px 120 Manual 111 ...
Страница 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Страница 116: ......
Страница 117: ......