Menu B: Hot water
B C D H d s c l n t 2 3
2 0 0 S e c
Function for the direct hot water boiler.
This parameter is the integration time of the selected HW
temperature of the boiler.
Menu B: Hot water
B D D H d s c O f f 3
4 ° C
Function for the cascaded direct hot water boilers.
This parameter is the offset of the selected HW temperature
of the cascaded boilers.
Menu B: Hot water
B E D H d s c D i f 3
8 ° C
Function for the cascaded direct hot water boilers.
This parameter is the hysteresis of the selected HW temper-
ature of the cascaded boilers.
Menu B: Hot water
B F D H i s c D i f 4
5 ° C
Function for the indirect hot water supply of the boiler (tank).
This parameter is the hysteresis of the selected HW temper-
ature of the calorifier/tank.
Menu B: Hot water
B G D H i d e t g r a d
3 ° C
Function for the indirect hot water supply of the boiler (tank).
This parameter detects an (an accelerated) hot water de-
mand, when a larger (water) amount is being used.
Menu C: Cascade
C 1 M a x C a s c U n t
1 1
Function for the cascading of the boiler(s).
This parameter sets the total amount of cascaded boilers.
(Max. 12 boilers).
Menu C: Cascade
C 2 B u s a d d r e s s
0
Function for the cascading of the boiler(s).
This parameter determines the address of the boiler for the
total cascading control.
Master = 0, Slave 1 = 1 etc.
Menu C: Cascade
C 3 D H i c a s / m a s
0
Function for the cascading of the boiler(s).
This parameter determines if only the Master boiler or all
boil-ers of the cascade are used for indirect hot water.
0 = All
1 = Master
Содержание S-CB Px 120
Страница 2: ...S CB Px 120 Manual 2 ...
Страница 6: ...S CB Px 120 Manual 6 ...
Страница 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Страница 34: ...S CB Px 120 Manual 34 ...
Страница 111: ...S CB Px 120 Manual 111 ...
Страница 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Страница 116: ......
Страница 117: ......