S-CB Px 120 Manual
50
OUTDOOR GRAPH (see also next page)
P5 AC
Heat curve minimum outside temperature
°C
This sets the minimum outside temperature at which one wants the maximum flow temperature that is set.
P5 AD
Heat curve flow temperature at minimum
°C
This sets the desired maximum flow temperature at the set minimum outside temperature.
P5 AE
Heat curve maximum outside temperature
°C
This sets the maximum outside temperature at which one wants the minimum flow temperature that is set.
P5 AF
Heat curve flow temperature at maximum
°C
This sets the desired minimum flow temperature at the set maximum outside temperature.
P6 BC
Heat curve Parallel Shift
°C
The heating curve is set by the parameters. Next to these setting done by the installer, the end user has the free-
dom to influence the flow temperature by doing a parallel shift setting. In this parameter the margins are set within
which the user can increase and decrease the calculated flow temperature relative to the calculated flow tempera-
ture by the heating curve that is set.
The actual parallel shift that is set by the user within the bandwidth allowed according to “P5AQ Max Heat curve
Parallel Shift”.
is continued
→
OUTSIDE TEMPERATURE
FL
O
W
TE
M
P
E
R
A
TU
R
E
TU
R
E
40
30
20
10
-40
-30
-20
0
-10
30
0
90
80
70
60
50
40
20
10
P5 AE
outside temp high
P5 AC
outside temp low
P5 AF
- Flow temp at
outside temp high
P5 AD
- Flow temp at outside temp low
P6 BC
- Parallel shift
HEATING CURVE
- main settings
Содержание S-CB Px 120
Страница 2: ...S CB Px 120 Manual 2 ...
Страница 6: ...S CB Px 120 Manual 6 ...
Страница 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Страница 34: ...S CB Px 120 Manual 34 ...
Страница 111: ...S CB Px 120 Manual 111 ...
Страница 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Страница 116: ......
Страница 117: ......