S-CB Px 120 Manual
54
10.13.
Checking the fault history
The following graphs describe how to check the fault history of the boiler.
Operating screen:
H E A T I N G : b o i l e r o f f
> > > : 1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Press [MENU]
Select "Faulthist" using [
◄
] & [
►
] and press [ENTER]
F a u l t h i s t
N o . 0 1
2 1 / 0 4 / 2 0 1 0 W e d 2 2 : 2 3 A
▲
blinking in turn
▼
S i p h o n S w i t c h
S v 9 9 9 / C U M 9 9 9 / R 9 9 9 9 , 5
Press [
◄
] & [
►
] to browse through the last 10 faults.
Press [MENU] or [ENTER] to exit. The unit will return to the
operating screen.
The fault menu shows the last 10 faults. For each fault the
display blinks between the two screens shown above. The top
line of the top screen shows the fault number and the bottom
line of the top screen shows the date, day and time the fault
occurred.
On the top line of the bottom screen the fault type is displayed.
The bottom line shows the following:
SV:
The total amount of this fault that has occurred after the
last time that the service history was erased (after service was
done).
CUM:
The total amount of this fault. The total amount cannot
be erased after service, this shows the fault history of the boil-
er (electronics) since the start of operation.
R:
Shows the elapsed time in hrs between the moment the
fault occurred and the moment it was reset.
Содержание S-CB Px 120
Страница 2: ...S CB Px 120 Manual 2 ...
Страница 6: ...S CB Px 120 Manual 6 ...
Страница 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Страница 34: ...S CB Px 120 Manual 34 ...
Страница 111: ...S CB Px 120 Manual 111 ...
Страница 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Страница 116: ......
Страница 117: ......