S-CB Px 120 Manual
60
Operating screen:
H E A T I N G : b o i l e r o f f
> > > : 1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Press [MENU]
Select "Parameter" using [
◄
] & [
►
] and press [ENTER]
Parameter menu:
I n s t a l l e r c o d e
0 0 0 0
Enter the 4-digit code with the [
◄
] & [
►
] and the [
▲
] & [
▼
]
buttons and select [ENTER]
The code will blink a few seconds and when entered correct-
ly, the following parameters will be displayed.
NOTICE: These codes are user based and give access to a
selected amount of parameters, which can be changed (In-
staller level 1/2).
Menu A: Heating
A 1
S t e p m o d u l
1
Function to activate the step modulation:
0 = Off
1 = On
Menu A: Heating
A 2
H E s o f f 1 3
4 ° C
CH supply temperature setting. This parameter is the offset of
the programmed CH temperature.
Menu A: Heating
A 3
H E s P r b 1 3
2 5 ° C
Select the CH supply temperature control. This parameter is
the proportional range of the selected CH supply tempera-
ture.
Menu A: Heating
A 4
H E s c D i f 1 3
1 0 ° C
Select the CH supply temperature control. This parameter
is the hysteresis of the selected CH supply temperature.
Menu A: Heating
A 5
H E s
l n t 1 3
6 0 S e c
Select the CH supply temperature control. This parameter is
the integration time of the selected CH supply temperature.
Menu A: Heating
A 6 H E
c O f f 3
4 ° C
Select the cascaded boilers supply temperature control.
This parameter is the offset of the selected CH supply tem-
perature of EACH boiler of the total cascade.
Содержание S-CB Px 120
Страница 2: ...S CB Px 120 Manual 2 ...
Страница 6: ...S CB Px 120 Manual 6 ...
Страница 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Страница 34: ...S CB Px 120 Manual 34 ...
Страница 111: ...S CB Px 120 Manual 111 ...
Страница 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Страница 116: ......
Страница 117: ......