By pressing the [SERVICE] button of the boiler, the boiler can be started without a heating demand. The boiler will
start to fire and also the pump will start to run. Firing of the boiler without a water flow (but filled with water) will
cause the so called “boiling noises”. Check during this “service function” operation also the flow and return tem-
peratures of the boiler by pressing the [
◄
] button once. The temperature difference of the flow and return must be
at least 13ºC and maximum 25ºC. This temperature difference indicates that there is a sufficient water flow over
the boiler; this water flow protects the heat exchanger against possible damage caused by a thermal overload.
Another safety feature of the boiler, to make sure that there is enough water flow over the boiler, is the monitoring
of the flow and return temperatures (T2 and T1). When the temperature difference (delta T) between the flow and
return exceeds a certain (set) value, the following warning messages will be shown in the display.
Display message
T 2 - T 1 h i g h
9 9 9 , 5 h r s
Reason:
Temperature difference T2-T1 has exceeded the blocking value, as set
in the parameters.
Display message
H e a t e x c h a n g a t r i s k
9 9 9 , 5 h r s
Reason:
Temperature difference T2-T1 has exceeded the blocking value more
than three times.
Set in the parameters P2 CQ-P2 CV (
∆
T>P2 CV (within t=P2 CQ).
When this T2-T1 value exceeds the lock-out setting, the boiler will switch off and the following lock out code will
be shown at the display.
Display message
F16
F l o w R e t u r n d t f a u l t
p u m p o n
9 9 9 , 5 h r s
Reason:
Temperature difference T2-T1 has exceeded the blocking value.
Programmed at the parameters P2 CO, P2 CR until P2CV.
When these messages appear and/or the boiler will lock out, it means that there is not enough flow over the boi-
ler. In this case check the functioning of the pump.
The boiler has no built in water flow switch. If there is the possible risk of a water flow blockage of the (external)
heating system, the following pre-cautions can be taken to ensure a water flow over the boiler:
•
Separate the boiler circuit from the (external) heating circuit by using a low loss header or plate heat ex-
changer.
•
When the boiler is not equipped with an internal (built in) water pressure switch, install a water pressure
switch externally, in series with the room thermostat.
During and after the commissioning of the boiler, the operation of the boiler pump must be checked, before lea-
ving the installation room.
NOTICE: Always check the running of the pump before firing the boiler.
Содержание S-CB Px 120
Страница 2: ...S CB Px 120 Manual 2 ...
Страница 6: ...S CB Px 120 Manual 6 ...
Страница 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Страница 34: ...S CB Px 120 Manual 34 ...
Страница 111: ...S CB Px 120 Manual 111 ...
Страница 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Страница 116: ......
Страница 117: ......