S-CB Px 120 Manual
11
FLUE SYSTEM
min-max:
CO
2
flue gas
3
G25/G20
%
8,5 - 9,0
G31
1
%
9,6 - 10,3
G30 (B/P)
1
%
9,6 - 10,4
NOx class [EN483 / EN15420]
-
5
NOx emission at 0% O
2
,
year emission
ppm
22,2
mg/kWh
39,9
Temp. flue gas at combustion air temp.
20°C
°C
≈
85-95
Available pressure for the flue system
4
Pa
160
INSTALLATION
Max. flow temperature
°C
90
Hydraulic resistance of the boiler at
Δ
T =
20 K
Head mWC 3,8
Hydraulic resistance of the boiler at
Δ
T =
25 K
Head mWC 2,4
Pressure CH-system min./max.
5
bar
1-4
ELECTRIC
Power supply
V / Hz
230 / 50
Power consumption
W
150
Protection class
-
IPX4D
NOTES
3
CO
2
of the unit measured/set without the boiler door in place
4
Maximum combined resistance of flue gas and air supply piping at high fire
5
With a pressure switch instead of the standard sensor, pressure may go up to 6,0 bar
Содержание S-CB Px 120
Страница 2: ...S CB Px 120 Manual 2 ...
Страница 6: ...S CB Px 120 Manual 6 ...
Страница 33: ...S CB Px 120 Manual 33 9 4 Electrical schematics ...
Страница 34: ...S CB Px 120 Manual 34 ...
Страница 111: ...S CB Px 120 Manual 111 ...
Страница 115: ...S CB Px 120 Manual 115 weather dependent control 49 73 ...
Страница 116: ......
Страница 117: ......