Order number: 900318.002 V0.31
Page 7
© Störk-Tronic 2021 • www.stoerk-tronic.com • Subject to modifications.
Parameter tables
Parameters
Name Function
Range
J1=0
A 0
Alarm suppression time after power on
1 ... 1440 min
1
A 2
Alarm suppression time after set point change
1 ... 1440 min
1
A 8
Alarm repetition - short period
1 ... 1440 min
1
A 9
Alarm repetition - long period
1 ... 48 h
1
A10
Limiter 1 mode
0: Deactivated
1: Limiter alarm low (A1L)
2: Limiter alarm high (A1H)
3: Limiter alarm low/high (A1L/A1H)
4: Limiter enable out (no alarm, inside
Low/High OK band)
2
A11
Limiter 1 - current value - sensor selection
1: F01
2: F02
3: F03
4: F04
5: F05
6: F06
7: VF1
8: VF2
9: VF3
10: VF4
1
A12
Limiter 1 low set point selection
0: Absolute
1: Set point (S1A/B/C) (Level C)
2: S2A/B (E-Level)
1
A13
Limiter 1 low set point offset
-199.0 ... 999.0 °C / K
-2.0
A14
Limiter 1 high set point selection
See
A12
0
A15
Limiter 1 high set point offset
-199.0 ... 999.0 °C / K
205.0
A16
Limiter 1 Hysteresis
0.1 ... 99.0 K
15.0
A17
Delay Limiter 1 overrun to error generation (0->1) (A1L, A1H)
0 ... 999 s
20
A18
Delay Limiter 1 values back to the accepted range (1->0) (A1L,
A1H)
0 ... 999 s
0
A19
Alarm suppression Limiter 1
0: Deactivated
+1: Power on (
A0
)
+2: reserved
+4: Set point changed (
A2
)
0
A1A
Limiter 1 assigned error unit
1: Unit 1
2: Unit 2
3: Unit 3
4: Unit 4
1
A20
Limiter 2 mode
See
A10
2
A21
Limiter 2 - current value - sensor selection
See
A11
0
A22
Limiter 2 low set point selection
See
A12
1
A23
Limiter 2 low set point offset
-199.0 ... 999.0 °C / K
-2.0
A24
Limiter 2 high set point selection
See
A12
1
A25
Limiter 2 high set point offset
-199.0 ... 999.0 °C / K
+2.0
A26
Limiter 2 Hysteresis
0.1 ... 99.0 K
0.5
A27
Delay Limiter 2 overrun to error generation (0->1) (A2L, A2H)
0 ... 999 s
0
A28
Delay Limiter 2 values back to accepted range (1->0) (A2L, A2H)
0 ... 999 s
0
A29
Alarm suppression Limiter 2
See
A19
0
A2A
Limiter 2 assigned error unit
See
A1A
1
A70
Reset min/max value storage
+1: Reset
A72
(Limiter 1 min)
+2: Reset
A73
(Limiter 1 max)
+4: Reset
A73
(Limiter 2 min)
+8: Reset
A74
(Limiter 2 max)
0