Parameter tables
E--
Control circuit 2
This circuit serves as a secondary circuit or freely definable thermostat.
It has no pre-defined function with the controller and may be used to handle anything, that can be handled with a simple Two-point or
PID-controller.
Para-
meter
Functional description
Setting range
J1=0
J1=1
E 1
Emergency mode duty cycle (Negative values for emergency cooling,
positive values for emergency heating)
-100 … 100 %
20.0
E10
Setpoint circuit 2 A
E13
...
E14
°C
150.0
E11
Setpoint circuit 2 B
E13
...
E14
°C
180.0
E13
Setpoint limitation below
-199.0 …
E14
°C
0.0
E14
Setpoint limitation above
E13
... 999.0 °C
999.0
E20
Mode
0: Deactivated
1: TP - (Two point, thermostat)
2: PID - (
E23
: Delta)
2
E21
Sensor for control circuit 2
0: Disabled
1: F1
2: F2
3: F3
4: F4
5: F5
6: F6
7: Virtual Sensor VF1
1
E22
Setpoint selection
see
C22
2
E23
Setpoint adjustment circuit 2
-199.0 ... 999.0 K
0.0
E24
Thermostat hysteresis
0.1…100.0 K
2.0
E25
Offset; 0%: One-sided (towards on); 50%: Symmetrical
0.0 ... 100.0 %
0
E26
Switching direction circuit 2
Applies to 2-point and PID controller
0: Off
1: Cool
2: Heat
2
E30
PID Function mode
0: Deactivated
+1: P
+2: I
+4: D
+8: Averaged over Period
7
E34
Proportional band (P-band)
0.1 ... 999.0 K [Unit
C21
]
1.0 K
E35
Reset time Tn (I-time)
0 ... 999 sec
60
E36
Lead time Tv (D-time)
0 ... 999 sec
0
E37
PID Backtracking
0.00 ... 2.00
0.00
E38
PID cycle time
1 ... 900 sec
5
E39
PID_OUT MAX (
E20
= 2)
100% is the absolute maximum output heating, 0% is no heating
0.0 ... 100.0 %
100.0
E3A
PID_OUT_MIN (
E20
= 1)
-100% is the absolute maximum output cooling, 0% is no cooling
-100.0 % ... 0.0 %
-100.0
E40
Internally used
...
E49
E99
Password
-99 ... 999
0