Error handling
Error units
A list of the available error units, which may be adjusted by the user.
The error units aggregate errors with a similar severity in order to provide easier configuration to their behavior.
Error
unit
Parameter
for actuators
Parameter for
acknowledge
Parameter
for repeat
Default actuators
General meaning of this error unit
1
A80
A81
A82
Buzzer, Display, warning (14)
Sensor Error, the device will switch into
emergency operation
2
A83
A84
A85
Buzzer, Display, error out
Operation of the device not possible, safety
relevant Errors
3
A86
A86
A87
Buzzer, Display, warning (14)
Operation impeded, but may continue
4
A89
A90
A91
-
Actuators
Each error unit has its own set of configurable actuators. These will be raised, if an error activates the corresponding error unit.
Name
Value
Effect
Error
+1
The global Error bit will be set
Warning
+2
The global warning bit will be set
Display
+4
The display will show the error in a blinking manner
Buzzer
+8
A noisy buzzer, to get the attention of the user
Acknowledge
Parameters
A81
,
A84
,
A87
and
A90
specify, how the error system is supposed to behave, if an error vanished, or gets acknowledged.
Value Mode
Comment
0
auto buzzer, auto clear
The buzzer goes quiet as soon as the error cause is removed, or an acknowledge happens.
When the error cause is removed, the other error actuators and notification stops.
1
auto buzzer, manual clear
The buzzer goes quiet as soon as the error cause is removed, or an acknowledge happens. The
other error actuators and notifications only stop after the error cause is removed and also was
acknowledged.
2
auto buzzer, restart clear
The buzzer goes quiet as soon as the error cause is removed, or an acknowledge happens. The
reset of the other actuators and notification requires a power-on-reset.
3
manual buzzer, manual clear
The buzzer only goes quiet, once the error is acknowledged. The other error actuators and noti-
fications only stop after the error cause is removed and also was acknowledged.
4
manual buzzer, restart clear
The buzzer only goes quiet, once the error is acknowledged. The reset of the other actuators and
notification requires a power-on-reset.
Error repetition
If the error cause is not removed but was acknowledged, the error units may raise the notification and actuators again after a specified time.
The selection happens through
A82
,
A85
,
A88
,
A91
.
Value
Meaning
0
No repetition
1
The actuators and notification are raised again, if the error cause was not removes
A8
minutes after the acknowledge
2
The actuators and notification are raised again, if the error cause was not removes
A9
minutes after the acknowledge