Order number: 900318.002 V0.31
Page 16
© Störk-Tronic 2021 • www.stoerk-tronic.com • Subject to modifications.
Parameter tables
F--
Fan - CVBC
(Honeywell Combined Valve Boiler Control)
This level contains parametrization for the Honeywell c-bus Burner controllers, which may be configured and controlled via Modbus.
Para-
meter
Functional description
Setting range
J1 = 0
J1 = 1
F 0
CVBC: Fan speed during ignition
0 ... 100 %
100
F 1
CVBC: interruption mode
0 ... 254: off
255: on
0
F 2
CVBC: Fan Kp high factor
0 ... 127
50
F 3
CVBC: Fan Ki high factor
0 ... 255
50
F 4
CVBC: Fan Kp low factor
0 ... 127
50
F 5
CVBC: Fan Kp low factor
0 ... 255
50
F 6
CVBC: Stabilization time
0 ... 255 sec
10
F 7
CVBC: Max fan rpm
6 ... 255 (*50 RPM)
10
F 8
CVBC: Min fan rpm
6 ... 255 (*50 RPM)
10
F 9
CVBC: Continuous fan rpm
6 ... 255 (*50 RPM)
10
F10
CVBC: Ramp steepness fan
0 ... 255 (*50 RPM / sec)
10
F11
CVBC: Fan configuration
Continuous
Control type
Modulation
0:
Of
Modulation
0 ... 10V
1:
On
Modulation
0 ... 10V
2:
Of
On/Off
N/A
3:
On
On/Off
N/A
4:
Off
Modulation
4 ... 20mA
5:
On
Modulation
4 ... 20mA
2
F12
CVBC: APS configuration
0 ... 255
0
F13
CVBC: APS switch over time
0 ... 50 sec
50
F20
CVBC: Pre-surge time
15299
10
F21
CVBC: Post-surge time
15299
10
F30
OEM Error Code Error history 0
-
0
F31
OEM Error Code Error history 1
-
0
F32
OEM Error Code Error history 2
-
0
F33
OEM Error Code Error history 3
-
0
F34
OEM Error Code Error history 4
-
0
F35
OEM Error Code Error history 5
-
0
F36
OEM Error Code Error history 6
-
0
F37
OEM Error Code Error history 7
-
0
F40
Time Error history 0
-
0
F41
Time Error history 1
-
0
F42
Time Error history 2
-
0
F43
Time Error history 3
-
0
F44
Time Error history 4
-
0
F45
Time Error history 5
-
0
F46
Time Error history 6
-
0
F47
Time Error history 7
-
0
F50
Burner cycles
-
0
F51
Lockout errors
-
0
F52
Burner running hours
-
0
F53
Burner hours
-
0
F99
Password
-99 ... 999
0