Parameter tables
J--
Parameter sets / Display configuration
This level contains general settings for the device, and it’s parameter handling.
Additionally, any parameter or counter resets in level N-- or t-- need to be unlocked here, first.
Para-
meter
Functional description
Setting range
J1 = 0
J1 = 1
J 1
Pre-defined parameter Set
0…20
0
1
J 2
Parameter reset
(Bit mask, add up values)
0: deactivated
+1: Set points
+2: Parameters
+4: Runtime
+8: Passwords
0
J 3
Mode after power on
0: OFF
1: ON
2: Last state
0
J 4
Start prelevel
0: Adr
1: PA
2: USr
0
J 5
Mask active prelevel
(Bit mask, add up values)
0: Nur PAL
+1: Adr
+2: PA
+4: USr
7
J 6
Mask active prelevel - standby
(Bit mask, add up values)
0: Nur PAL
+1: Adr
+2: PA
+4: USr
7
J 7
Fryer style
0: Störk-Tronic default
1:
1
J10
Display 1
0: Disabled
1: F1
2: F2
3: F3
4: F4
5: F5
6: F6
1
J11
Resolution
0: Full numbers
1: 0.5
2: 0.1
2
J12
Display during standby
0: deactivated
1:
OFF
2:
AUS
3: DP right
4:
Stb
1
J13
Unit
0: °C
1: °F
0
J14
Display brightness
0 % ... 100 %
100
J42
Unlock counter reset
0: no action
1: unlock counter/timer reset for
J44
seconds
0
J43
Reset actions after unlock
0: As many reset operations possible, as possible
1: Only 1 reset operation per unlock
1
J44
Reset unlock time
1 ... 999 sec
600
Jr1
Software version
x.yy
PA
Password parameter levels
-99 ... 999
0
J99
Password
-99 ... 999
0