3. To configure the PA15 for this operating mode, plug in the
“SOLAR MANAGER” jumper.
Nightlight
Buzzer
SOC
Manager
Exc ess
Solar
Manager
4. Set the identifier (or ID number) to adjusting controller “P2”. The
setting on “P1” is also ignored in this operating mode. Settings
from 0..8 are accepted. The setting 9 is possible, but has exactly
the same functionality as position 8. This means that a
maximum of 9 additional solar arrays can be included in the
system.
P1
P2
Position not
relevant !
Solar generator
identifier
15 A
A+ A- S
S L+ L-
Sola r
Manager
Exc ess
SOC
Manager
Nightlight
Buzzer
PA 15
P1
P2
The additional generator with the allocation “8” has the highest
priority and is activated first and deactivated last
.
“0” has the lowest priority.
The identifiers or ID values are created depending on the
current battery voltage and the final charge voltage.
The closer the current battery voltage comes to the final charge
voltage, the higher the identifier transferred and the more
additional generators are shut down!
PA15 TTS Operating Manual
Page 23