The beeps sounded when resetting the adjusting controller are normal and
are intended to help you set the required values more easily.
The beep signals the transition between two setting options, e.g. starting
from the far left 0, turn 4 beeps to the right = 4. SOC values between
<10% and >99 % can be set on the scale from 0 – 9.
0 : SOC between 0 ... 9% (<10 %)
beep
1 : SOC between 10 ... 19% (<20 %)
beep
....
beep
8 : SOC between 80 ... 89% (<90 %)
beep
9 : SOC between 90 ... 99% (<100 %)
5.
The activation threshold (hysteresis) is the SOC value at which the
consumer device is to be reactivated. This value can be set on “P2”.
Position “3” would mean, for example, that the load is switched back on
when the SOC <= 30%.
The beep signals the transition between two setting options, e.g. starting
from the far left 0, turn 4 beeps to the right = 4. SOC values between
<10% and >99 % can be set on the scale from 0 – 9.
0 : SOC between 0 ... 9% (>=10 %)
beep
1 : SOC between 10 ... 19% (>=20 %)
beep
....
beep
8 : SOC between 80 ... 89% (>=80 %)
beep
9 : SOC between 90 ... 99% (>=90 %)
6. Please note that for this operating mode to function correctly, the
value at “P1” must always be less than the value at “P2”!
SOC manager function only when: P1 < P2
If this condition is not fulfilled, the Generator Manager function is
automatically active, which has the opposite function, see section 4.4
The load output is always enabled if either the SOC value is greater than
the shutdown value, or, following shutdown, the SOC is once again
greater than the activation value (P2).
When making the electrical connections, please always observe
section 3. In standalone systems, earthing of the components is not
necessary, not standard or may be prohibited by local regulations (e.g.
PA15 TTS Operating Manual
Page 16