The beep signals the transition between two setting options, e.g.
starting from the far left 0, turn 4 beeps to the right = 4. SOC values
between <10% and >90 % can be set on the scale from 0 – 9.
0 : SOC between 0 ... 9% (>= 10% --> OFF; <10% --> ON)
beep
1 : SOC between 10 ... 19% (>= 20% --> OFF; <20% --> ON)
beep
....
beep
8 : SOC between 80 ... 89% (>= 80% --> OFF; <80% --> ON)
beep
9 : SOC between 90 ... 99% (>= 90% --> OFF; <90% --> ON)
The adjusting controller P2 must be set to a smaller value than P1
for this operating mode.
6. Now set the activation threshold on “P2”. The activation threshold is
the SOC value at which the PA15 output is to start the generator.
At e.g. the value “4”, the generator will be started, if the SOC is below
40%.
If this value is reached, the PA15 will connect its load output to the
battery until the shut-down threshold (of P1) is reached.
The beep signals the transition between two setting options, e.g.
starting from the far left 0, turn 4 beeps to the right = 4. SOC values
between <10% and >90 % can be set on the scale from 0 – 9.
0 : SOC between 0 .. 9% (<10%)
beep
1 : SOC between 10 .. 19% (<20%)
beep
. . .
beep
8 : SOC between 80 .. 89% (<90%)
beep
9 : SOC between 90 .. 99% (<100%)
7. Please note that for this operating mode to function correctly, the
value at “P1” must always be greater than the value at “P2”!
Generator manager function only when :
P1 > P2
If this condition is not fulfilled, the SOC MANAGER function is
automatically active, which has the opposite function, see section
4.4
PA15 TTS Operating Manual
Page 20