The Tarom / Powertarom transfers the following system information:
•
Current SOC VALUE,
•
Identifier for the generator manager
•
Identifier for the excess manager (EXCESS)
•
DAY / Night information
In accordance with this setting, the PA15 TTS remote switch will only react
to the signals sent if it receives the information transferred at least 3 times
without error.
This transfer protection features, realised using multiple reception, may
result in delays in the switch response. The shortest delay time is around 4
minutes.
If the information itself changes within the required triple information
transfer (e.g. the SOC changes from 60% to 59%), a third transfer of the
new value will be required.
If the PA15 is unable to receive any correct signals, permanently specified
safety functions become active in order to protect the system (e.g. load
shut-off).
During data transfer, the power consumption of the TAROM /
POWERTAROM charge controller increases for a short time. For this
reason, this mode should be deactivated if not being used.
4.3 Decentralised power management (SOC MANAGER P1<P2)
4.3.1 What does this mean?
Decentralised power management can be used to assign different
priorities to the consumer equipment in your standalone network,
and enable or block them automatically regardless of the SOC. One
or more external buttons can be connected to the device to be able
to switch your consumer device on and off more easily.
You can also choose whether or not you want an acoustic early
warning before the consumer device connected is shut down.
The SOC information is transferred to the battery lead by the
Solarix Tarom charge controller via up-modulated signals, see
section 4.2.
4.3.2 How to do this
1. Connect the PA15 to your battery lead with the correct polarity
(A+ / A-).
2. Connect the consumer device to the output on the PA15 (L+ 7/
L-) with the correct polarity.