IM-P198-05
MI Issue 2
98
5.10 ANNEX - BACnet protocol implementation conformance
statement
Date:
19-April-2012
Applications Software Version:
1.07
Firmware Revision:
N/A
BACnet Protocol Revision:
4
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
5.10.1 List all BACnet interoperability building blocks supported (Annex K):
BIBBs
DS-RP-B
DS-WP-B
DM-DDB-B
DM-DOB-B
DM-dcC-B
DS-RPM-B
DS-WPM-B
Services supported
Read Property
Execute
Write Property
Execute
Read Property Multiple
Execute
Write Property Multiple
Execute
Who-Is
Execute
I-Am
Initiate
Who-Has
Execute
I-Have
Initiate
Device Communication Control
Execute