4.8 Totalizer #1 menu
Use the Totalizer Menu to configure and monitor the totalizer. The totalizer output is a 50
millisecond (.05 second) positive pulse (relay closed for 50 milliseconds). The totalizer cannot
operate faster than one pulse every 100 millisecond (0.1 second). A good rule to follow is to
set the unit per pulse value equal to the maximum flow in the same units per second. This
will limit the pulse to no faster than one pulse every second.