4.10 Energy menu - For EM energy meters only
Configuration:
There are several possibilities regarding the measurement of water or steam energy given
the location of the meter and the use of a second RTD. The table below summarizes the
possibilities:
Fluid
Meter location
Second RTD
Measurement
Water
"Sent" Flow Line
"Return Flow Line
Change in Energy
Water
"Return" Flow Line "Sent" Flow Line
Change in Energy
Water
"Sent" Flow Line
None
Outgoing Energy
Steam
"Sent" Flow Line
"Return" Flow Line (condensate)
Change in Energy
Steam
"Sent" Flow Line
None
Outgoing Energy
As above, you must properly configure the meter in the Energy Menu.
1.
Loc in Sent Flow? Select Yes or No based on where the meter is located. Refer to the
above table
2.
Heating System? Select Yes for a hot water system used for heating. Select No for a chilled
water system used for cooling. Always select Yes for a steam system.
3.
% Returned. Select a number between 0% and 100%. Estimate the amount of water that
returns.
It is usually 100%, or can be less than 100% if historical data shows the amount of makeup
water used. If a second RTD is not used, set to 0%. When 0% is selected, the energy
calculation represents the outgoing energy only (no return energy is subtracted).
NOTE: the meter ships from the factory assuming 0% return and has a 1000 ohm
resistor installed in the RTD #2 wiring location. This needs to be removed if the meter
is to be used in a manner other than with 0% return and with the customer supplied
RTD in its place.
Содержание RIM20
Страница 49: ...IM P198 05 MI Issue 2 49 Run mode screens Press Exit to return to Run mode Use keys to access each item...
Страница 50: ...IM P198 05 MI Issue 2 50 4 3 Using the set up menus Run mode screens...
Страница 52: ...IM P198 05 MI Issue 2 52 4 5 Output menu...
Страница 56: ...IM P198 05 MI Issue 2 56 4 7 Alarms menu Energy EM meters only...
Страница 66: ...IM P198 05 MI Issue 2 66 4 14 Diagnostics menu...
Страница 132: ...IM P198 05 MI Issue 2 132...