3.10 Installation of meters with packing gland connection
(No Insertion Tool)*
Use the following formula to determine insertion depth for meters with a packing gland
connection (NPT and flanged) without an insertion tool.
Fig. 11 Insertion calculation (Meters without insertion tool)
Example:
To install a RIM20 flowmeter with a standard probe (S = 728.218 mm (28.67")) into a DN350
(14") schedule 40 pipe, the following measurements are taken:
F = 76.2 mm (3") R = 127 mm (5") t = 11.125 mm (0.438")
The example insertion length is 513.842 mm (20.23").
Insertion length formula
I = S - F - R - t
Where:
I
= Insertion length.
S
= Stem length - the distance from
the center of the sensor head
to the base of the enclosure
adapter
S
= 728.218 mm (28.67") for
standard probes;
S
= 1 033.02 mm (40.67") for 304.8
mm (12") extended probes.
F
= Distance from the raised face
of the flange or top of NPT
stem housing to the outside of
the pipe wall.
R
= Pipe inside diameter ÷ 2 for
pipes DN250 (10") and smaller.
R
= 127 mm (5") for pipe diameters
larger than 250 mm (10").
t
= Thickness of the pipe wall.
(Measure the disk cut-out
from the tapping procedure or
check a piping handbook for
thickness.)
*
All dimensions
are in mm
(inches)
EXIT
EN T ER
I
F
R
t
Flow
S
Содержание RIM20
Страница 49: ...IM P198 05 MI Issue 2 49 Run mode screens Press Exit to return to Run mode Use keys to access each item...
Страница 50: ...IM P198 05 MI Issue 2 50 4 3 Using the set up menus Run mode screens...
Страница 52: ...IM P198 05 MI Issue 2 52 4 5 Output menu...
Страница 56: ...IM P198 05 MI Issue 2 56 4 7 Alarms menu Energy EM meters only...
Страница 66: ...IM P198 05 MI Issue 2 66 4 14 Diagnostics menu...
Страница 132: ...IM P198 05 MI Issue 2 132...