IM-P198-05
MI Issue 2
81
Sequence
Description
Access Notes
1,4,1,1
PV
View
Primary variable value
1,4,1,2
PV Sensor Unit
Edit
Primary variable units
1,4,1,3
Sensor Information View
PV LSL, PV USL, PV Min span
1,4,2,1
Snsr Damp
Edit
Primary variable damping (time constant)
in seconds
1,4,2,2,1
PV LRV
Edit
Primary variable low range value
1,4,2,2,2
PV URV
Edit
Primary variable upper range value
1,4,2,3,1
PV LRV
Edit
Primary variable low range value
1,4,2,3,2
PV URV
Edit
Primary variable upper range value
1,4,2,4
Xfer Fnctn
View
Linear
1,4,2,5
AI % rnge
View
Analogue output % range
1,4,3,1,1
AO1
View
Analogue output, mA
1,4,3,1,2
AO alarm typ
N/A
Not used
1,4,3,1,3,1
4 mA
View
Loop test, fix Analogue output at 4 mA
1,4,3,1,3,2
20 mA
View
Loop test, fix Analogue output at 20 mA
1,4,3,1,3,3
Other
Edit
Loop test, fix Analogue output at mA value
entered
1,4,3,1,3,4
End
Exit loop test
1,4,3,1,4
D/A trim
Edit
Calibrate electronics 4 mA and 20 mA values
1,4,3,1,5
Scaled D/A trim
N/A
Not used
1,4,3,2,1
Poll addr
Edit
Poll address
1,4,3,2,2
Num req. preams
View
Number of required preambles
1,4,3,2,3
Burst mode
N/A
Not used
1,4,3,2,4
Burst option
N/A
Not used
1,4,4,1
Distributor
N/A
Not used
1,4,4,2
Model
N/A
Not used
1,4,4,3
Dev id
View
Device identification
1,4,4,4
Tag
Edit
Tag
1,4,4,5
Date
Edit
Date
1,4,4,6
Write Protect
View
Write protect
1,4,4,7
Descriptor
Edit
Turbine flowmeter
1,4,4,8
Message
Edit
32 character alphanumeric message
1,4,4,9
PV snsr s/n
View
Primary variable sensor serial number
1,4,4,menu
Final assy #
Edit
Final assembly number
1,4,4,menu,1
Universal Rev
View
Universal revision
1,4,4,menu,2
Fld dev Rev
View
Field device revision
1,4,4,menu,3
Software Rev
View
Software revision
1,5
Review
N/A
Not used
2
PV
View
Primary variable value
3
PV AO
View
Analogue output, mA
4,1
PV LRV
Edit
Primary variable lower range value
4,2
PV URV
Edit
Primary variable upper range value
5,1
PV LRV
Edit
Primary variable lower range value
5,2
PV URV
Edit
Primary variable upper range value
Содержание RIM20
Страница 49: ...IM P198 05 MI Issue 2 49 Run mode screens Press Exit to return to Run mode Use keys to access each item...
Страница 50: ...IM P198 05 MI Issue 2 50 4 3 Using the set up menus Run mode screens...
Страница 52: ...IM P198 05 MI Issue 2 52 4 5 Output menu...
Страница 56: ...IM P198 05 MI Issue 2 56 4 7 Alarms menu Energy EM meters only...
Страница 66: ...IM P198 05 MI Issue 2 66 4 14 Diagnostics menu...
Страница 132: ...IM P198 05 MI Issue 2 132...