IM-P198-05
MI Issue 2
82
5.5 Modbus communications
Warning!
Place controls in manual mode when making configuration changes to the
turbine meter.
5.5.1 Applicable flowmeter models
Spirax Sarco RIM20 Mass flowmeters with Modbus communication protocol and firmware
version 4.00.58 and above.
5.5.2 Overview
This document describes the preliminary implementation of the Modbus communication
protocol for use in monitoring common process variables in the Spirax Sarco RIM20 rotor
insertion flowmeter. The physical layer utilizes the half-duplex RS-485 port, and the Modbus
protocol.
5.5.3 Reference documents
The following documents are available online from www.modbus.org.
Modbus Application Protocol Specification V1.1
Modbus Over Serial Line Specification & Implementation Guide V1.0
Modicon modbus Protocol Reference Guide PI-MBUS-300 Rev. J
5.5.4 Wiring
An RS485 daisy chained network configuration as depicted below is recommended. Do not
use a star, ring, or cluster arrangement.
Fig. 51 RS-485 Wiring (MODBUS)
5.5.5 Pin Labeling (among devices)
"RS-485 -" ="A" ="TxD-/RxD-" ="Inverting pin"
"RS-485 +" ="B" ="TxD+/RxD+" ="Non-Inverting pin"
"RS-485 GND" ="GND" ="G" ="SC" ="Reference"
RS-485 -
RS-485 +
RS-485 GND
RS-485 Master
Turbine Meter
R
S
-4
85
-
R
S
-4
85
+
R
S
-4
85
G
N
D
R
S
-4
85
-
R
S
-4
85
+
R
S
-4
85
G
N
D
Other Device 2, etc.
R
S
-4
85
-
R
S
-4
85
+
R
S
-4
85
G
N
D
Other Device 1
Содержание RIM20
Страница 49: ...IM P198 05 MI Issue 2 49 Run mode screens Press Exit to return to Run mode Use keys to access each item...
Страница 50: ...IM P198 05 MI Issue 2 50 4 3 Using the set up menus Run mode screens...
Страница 52: ...IM P198 05 MI Issue 2 52 4 5 Output menu...
Страница 56: ...IM P198 05 MI Issue 2 56 4 7 Alarms menu Energy EM meters only...
Страница 66: ...IM P198 05 MI Issue 2 66 4 14 Diagnostics menu...
Страница 132: ...IM P198 05 MI Issue 2 132...