IM-P198-05
MI Issue 2
85
5.6 Register definitions
The meter serial number and those variables that are commonly monitored (mass, volume
and energy flowrates, total, pressure, temperature, density, viscosity, Reynolds number,
and diagnostic variables such as frequency, velocity, gain, amplitude and filter setting) are
accessible via the Modbus protocol. Long integer and floating point numbers are accessed
as pairs of 16-bit registers in the register order selected in the Modbus Order menu. Floating
point numbers are formatted as single precision IEEE 754 floating point values.
The flowrate, temperature, pressure, and density variables may be accessed as either the
flowmeter internal base units or in the user-programmed display units, which is determined
by the programming Output Menu’s"Modbus Units" item. The display units strings may be
examined by accessing their associated registers. Each of these units string registers contain
2 characters of the string, and the strings may be 2 to 12 characters in length with unused
characters set to zero. Note that the byte order affects the order in which the strings are
transmitted. If the Modbus Order menu (see page 2) is set to 0-1:2-3 or 2-3:0-1, then the
characters are transmitted in the correct order; if set to 1- 0:3-2 or 3-2:1-0, then each pair of
characters will be transmitted in reverse order.
Registers
Variable
Data type
Units
Function
code
Addresses
65100-65101
Serial number
unsigned long
—
03, 04
30525-30526
Totalizer
unsigned long
display
units*
03, 04
524-525
32037-32042
Totalizer units
string
—
03, 04
2036-2041
30009-30010
Mass flow
float
display
units*
03, 04
8-9
30007-30008
Volume flow
float
display
units*
03, 04
6-7
30005-30006
Pressure
float
display
units*
03, 04
4-5
30001-30002
Temperature
float
display
units*
03, 04
0-1
30029-30030
Velocity
float
ft/sec
03, 04
28-29
30015-30016
Density
float
display
units*
03, 04
14-15
30013-30014
Viscosity
float
cP
03, 04
12-13
30031-30032
Reynolds number
float
—
03, 04
30-31
30025-30026
Turbine frequency
float
Hz
03, 04
24-25
34532
Gain
char
—
03, 04
4531
30085-30086
Turbine amplitude
float
Vrms
03, 04
84-85
30027-30028
Filter setting
float
Hz
03, 04
26-27
Содержание RIM20
Страница 49: ...IM P198 05 MI Issue 2 49 Run mode screens Press Exit to return to Run mode Use keys to access each item...
Страница 50: ...IM P198 05 MI Issue 2 50 4 3 Using the set up menus Run mode screens...
Страница 52: ...IM P198 05 MI Issue 2 52 4 5 Output menu...
Страница 56: ...IM P198 05 MI Issue 2 56 4 7 Alarms menu Energy EM meters only...
Страница 66: ...IM P198 05 MI Issue 2 66 4 14 Diagnostics menu...
Страница 132: ...IM P198 05 MI Issue 2 132...