This is the upper flow limit alarm value that can be associated with a
discrete output. An alarm code is generated when the flow value exceeds
this limit. If no checking is needed, this value should be set to zero.
Press
OK (F4)
to accept the value.
This is the lower flow limit alarm value that can be associated with a
discrete output. An alarm code is generated when the flow value is below
this limit. If no checking is needed, this value should be set to zero.
Press
OK (F4)
to accept the value.
This is the upper temperature limit alarm value that can be associated
with a discrete output. An alarm code is generated when the temperature
value exceeds this limit. If no checking is needed, this value should be
set to zero.
HiFloAlm = 1234 SCFM
CHG OK
LoFloAlm = 100 SCFM
CHG OK
HiTmpAlm = 230 C
CHG OK
44
Operation: Programming
Programming
Using
the Local Display
High Flow Rate
Alarm
Low Flow Rate
Alarm
High Temp Alarm
Filter
Response (Sec.) 65% of
Target
0.09
0.10
0.8
0.15
0.7
0.20
0.6
0.25
0.5
0.30
0.4
0.35
0.3
0.40
0.2
0.60
0.1
1.00
0.05
2.00
0.03
3.00
0.01
10.3