Class I Equipment (Electrical Grounding Required for Safety).
Installation (Over-voltage) Category II for transient over-voltages.
Outputs:
Two isolated 4 to 20mA outputs (output one is for flow rate and output two is programmable for
flow rate or temperature); fault indication per NAMUR NE43.
Isolated pulse output 0 to 100Hz, 5 to 24 volts p/p for flow (the pulse output can be used as an
isolated solid state output for alarms); 10mA max.
Serial Communication:
USB communication port is standard. The free PC-based software tool - MTI10/MTL10 View™ -
provides complete configuration, remote process monitoring, and data logging functions.
Optional serial communication: RS485 Modbus.
4 to 20mA Loop Verification:
Simulation mode used to align 4 to 20mA output with the input to customer’s PLC/DCS.
Physical Specs
Sensor material:
316 stainless steel standard; Hastelloy C276 optional
Enclosure:
NEMA 4X (IP68), aluminum, dual conduit entries with ¾” NPT or optional M20 x 1.5mm.
Cabling
to remote enclosure: 5-conductor, 18 AWG, twisted, shielded, 100 feet maximum.
Retractor Assemblies:
Packing gland assembly: 125 psig (8.6 barg ) max.
High pressure (crank) retractor: NPT 600 psig (41.4 barg), ANSI 150 flange & ANSI 300 flange,
no valve supplied.
Insertion Flowmeter Installation:
Spirax Sarco-supplied compression fitting connects to customer-supplied ¾” female coupling
welded to pipe.
106
Appendices: Specifications