Entering data in Unit per Pulse:
Press
U/P (F2)
and the following screen will show:
Press
CHG (F1)
to change the setting and then
OK (F4)
to accept entry.
The value entered is in unit per pulse (i.e. 0.01 flow unit total per pulse)
Entering data with flow and maximum frequency:
Press
FEQ (F3)
and the following screen will show:
Enter the maximum frequency and press
OK (F4)
(Maximum frequency should not exceed 100 Hz)
The next screen will show:
Note: When the flow rate exceeds the maximum frequency set point, the
output will stay at that maximum frequency but the MTI10/MTL10 will
issue an alarm code.
Caution: Equation to ensure pulse rate must not exceed 100 Hz.
Alarm Output
To program the Alarm output, press
I/O (F1)
key from the "SET
PARAMETERS" menu screen, then select
I/O (F2)
and the screen will
show:.
Then press
OUT (F2)
and the screen may show:
UNT/PLS = 0.01
CHG OK
MaxFreq=98.5 Hz
CHG OK
MaxFlo=4999.8 SCFM
CHG OK
SET I/O
INP OUT EXIT
33
Operation: Programming
Programming
Using
the Local Display
Max Flow and
Frequency