Measurement Mode
In the measurement mode, there are four different display screens
(display 1, 2, 3 and a prompt screen to enter the programming mode),
two display screens are user programmable (refer to Display Setup p.
36). Scrolling through the display is accomplished by pressing the
F1 or F2 key to view the next or previous screen. Pressing the F1 and
F2 keys at the same time enters the Engineering Menu screens (display
10 through 26). Keys F1 and F2 are used to scroll through the different
screens and key F4 in order to exit to Display #1. Pressing the F3 and
F4 keys at the same time brings up the Reset Total screen (see p. 46)
prompt.
Fig. 4.2: MTI10/MTL10 Display Screen Navigation
Operation: Display Screens
Local Display
Screens
26
F1 key: Moves up one screen
F2 key: Moves down one screen
(User programable screen)
(User programable screen)
Enter “totalizer reset screen”
when F3 & F4 are pressed at
the same time
(Fixed screen)
Enter programming screen
Requires password.
Default is 1234.
Display #1
Display #2
Display #3
Display #4
(Fixed screen)
F1
F1
F1
F1
F2
F2
F4
F2
F2
F3
F4
1456.5 SCFM
123456 SCF
Elp = 14.6 HR
88.5˚ F
Alarm = None
Elp = 14.6 HR
Set Parameter?
No
Yes