Remove a DIMM
->
show faulty
Target | Property | Value
--------------------+-------------------+-------------------
/SP/faultmgmt/0 | fru | /SYS/MB/CMP0/MCU1/CH0/D0
/SP/faultmgmt/0 | timestamp | Dec 21 16:40:56
/SP/faultmgmt/0/ | timestamp | Dec 21 16:40:56 faults/0
/SP/faultmgmt/0/ | sp_detected_fault | /SYS/MB/CMP0/MCU1/CH0/D0
faults/0 | | Forced fail(POST)
2.
Locate the DIMM that corresponds to the listed name.
In this example,
/SYS/MB/CMP0/MCU1/CH0/D0
indicates the DIMM slot on the mother board that
is farthest from the power supplies.
Related Information
■
“Locate a Failed DIMM (LEDs)” on page 95
■
■
Remove a DIMM
Caution -
These procedures require that you handle components that are sensitive to ESD. This
sensitivity can cause the component to fail. To avoid damage, ensure that you follow antistatic
practices as described in
.
You can perform this procedure. The system must be completely powered down before
performing this procedure. See
“Component Service Categories” on page 49
information about cold-service procedures.
Perform this procedure to remove a faulty DIMM from the motherboard.
1.
Locate the DIMM to be removed.
“Locate a Failed DIMM (LEDs)” on page 95
and
.
2.
Remove the faulty DIMM.
a.
Press down both DIMM slot ejector tabs as far as they can go.
Servicing DIMMs
97
Содержание S7-2L
Страница 1: ...SPARC S7 2L Server Service Manual Part No E73201 04 March 2017...
Страница 2: ......
Страница 10: ...10 SPARC S7 2L Server Service Manual March 2017...
Страница 25: ...Device Paths Internal Component Locations on page 20 Device Paths on page 23 Identifying Components 25...
Страница 26: ...26 SPARC S7 2L Server Service Manual March 2017...
Страница 44: ...44 SPARC S7 2L Server Service Manual March 2017...
Страница 61: ...Remove the Fan Cover Use a T6 Torx screwdriver Preparing for Service 61...
Страница 64: ...64 SPARC S7 2L Server Service Manual March 2017...
Страница 76: ...76 SPARC S7 2L Server Service Manual March 2017...
Страница 86: ...86 SPARC S7 2L Server Service Manual March 2017...
Страница 92: ...Verify a Power Supply Rear Panel Components on page 19 92 SPARC S7 2L Server Service Manual March 2017...
Страница 156: ...156 SPARC S7 2L Server Service Manual March 2017...