Clear a Fault Manually
Clear a Fault Manually
When the server detects faults, the faults are logged and displayed on the console. In most
cases, after the fault is repaired the fault condition is repaired automatically. In cases where the
fault condition is not automatically cleared, you must clear the fault manually.
1.
After replacing a faulty component, power on the server, and verify that the fault
for that component has cleared.
Use the
fmadm faulty
command to confirm that the fault is clear.
2.
Determine your next step.
■
If no fault was detected, you do not need to do anything else. Do not perform
the subsequent steps.
■
If a fault was detected, continue to the next step.
3.
Clear the fault from all persistent fault records.
In some cases, even though the fault is cleared, some persistent fault information remains
and results in erroneous fault messages at boot time. To ensure that these messages are not
displayed, type:
faultmgmtsp>
fmadm replaced
FRU
Fault UUID numbers are displayed in
fmadm faulty
output.
4.
If required, reset the server.
In some cases, the output of the
fmadm
faulty
command might include this message for the
faulty component:
faulted
and
taken
out
of
service
.
If this message appears in the output, you must reset the server after you manually repair the
fault.
faultmgmtsp>
exit
->
reset /System
Are you sure you want to reset /System?
y
Resetting /System ...
5.
Clear the fault in the Oracle Enterprise Manager Ops Center software, if
applicable.
42
SPARC S7-2L Server Service Manual • March 2017
Содержание S7-2L
Страница 1: ...SPARC S7 2L Server Service Manual Part No E73201 04 March 2017...
Страница 2: ......
Страница 10: ...10 SPARC S7 2L Server Service Manual March 2017...
Страница 25: ...Device Paths Internal Component Locations on page 20 Device Paths on page 23 Identifying Components 25...
Страница 26: ...26 SPARC S7 2L Server Service Manual March 2017...
Страница 44: ...44 SPARC S7 2L Server Service Manual March 2017...
Страница 61: ...Remove the Fan Cover Use a T6 Torx screwdriver Preparing for Service 61...
Страница 64: ...64 SPARC S7 2L Server Service Manual March 2017...
Страница 76: ...76 SPARC S7 2L Server Service Manual March 2017...
Страница 86: ...86 SPARC S7 2L Server Service Manual March 2017...
Страница 92: ...Verify a Power Supply Rear Panel Components on page 19 92 SPARC S7 2L Server Service Manual March 2017...
Страница 156: ...156 SPARC S7 2L Server Service Manual March 2017...