animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
46/55
6.15
Menu index card “Radio inputs – Venetian blinds Up/Down”
6.15.1 Basic Function
Selected option:
Venetian blind, Up/Down
6.15.2 Long operation (action) after
Default value:
0.5 seconds
Selection options:
0.3...5.0 seconds
This parameter defines the activity time of the corresponding transmitter push button which distinguishes be-
tween the sending of a short-term telegram (Step/Stop) and a long-term telegram (Up/Down). If the time, for
example, is parameterized on 0.5 seconds, then only after a pressing of more than 0.5 seconds is a long-
term telegram generated. With a pressing of the push button which is shorter than 0.5 seconds, a short-term
telegram is generated.
6.15.3 Functionality of my push button
Default value:
No function
Selection options:
1-Bit value
8-Bit value
No function
6.15.3.1
1-Bit value
Default value:
On
Selection options:
On
Off
Toggle
No function
•
On
If the “my” button in the radio transmitter is pressed, the object value “On” is generated. The duration of the
activity is not evaluated.
•
Off
If the “my” button in the radio transmitter is pressed, the object value “Off” is generated. The duration of the
activity is not evaluated.
•
Toggle
If the “my” button in the radio transmitter is pressed, the object value toggles between “On” and “Off”. The
duration of the activity is not evaluated.
•
No function
If the “my” button in the radio transmitter is pressed, no object is generated.
H
See chapter 1 Definitions
for On (“1”) Off (“0”) Toggle (“1/0”).