animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
50/55
•
Off
If the “my” button in the radio transmitter is pressed, the object value “Off” is generated. The duration of the
activity is not evaluated.
•
Toggle
If the “my” button in the radio transmitter is pressed, the object value toggles between “On” and “Off”. The
duration of the activity is not evaluated.
•
No function
If the “my” button in the radio transmitter is pressed, no object is generated.
H
See chapter 1 Definitions
for On (“1”) Off (“0”) Toggle (“1/0”).
6.17.4.2
8-Bit value
Default value:
0
Selection options:
0
– 255
With this parameter the value (
0
– 255)
is set which is transmitted while pressing the “my” button in the radio
transmitter.
6.17.4.3
No function
If the “my” button in the radio transmitter is pressed, no object is generated.
6.18
Menu index card “Radio inputs – Dimming”
6.18.1 Basic Function
Selected option:
Dimming
6.18.2 Long operation (action) after
Default value:
0.5 seconds
Selection options:
0.3...5.0 seconds
This parameter defines the pressing time of the corresponding transmitter push button (Up/Down) which
makes a distinction between the sending of a short-term telegram (On/Off) and a long-term telegram
(Brighter/darker dimming). If the time, for example, is set at 0.5 seconds, a long-term telegram is generated
after a longer pressing than 0.5 seconds. With a pressing duration which is shorter than 0.5 seconds, a