animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
30/55
6.3.3 Block position orders (1 Byte) and IP2
Default value:
No
Selection options:
No
Yes
Position orders (byte) can be blocked per object (51-54) using this parameter. If a telegram with the value
“1”
is received on the corresponding object during a blinds move, this move is carried out up to the end. Only
then are further move commands (byte) blocked. If a telegram with the value
“0” is received on the corre-
sponding object, the move commands (byte) are released again.
6.3.4 Block slat orders (1 Byte)
Default value:
No
Selection options:
No
Yes
Slat orders (byte) can be blocked per object (51-54) using this parameter. If a telegram with the value
“1” is
received on the corresponding object when the Venetian blind is turning, this move is carried out up to the
end. Only then are further slat orders (byte) blocked. If a telegram with the value
“0” is received on the corre-
sponding object, the slat orders (byte) are released again.
6.3.5 Block Up/Down (1 Bit) and Intermediate Position 1 (IP 1)
Default value:
No
Selection options:
No
Yes
UP/DOWN orders (bit) can be blocked per object (51-54) using this parameter. If a telegram with the value
“1” is received on the corresponding object during a blinds move, this move is carried out up to the end. Only
then are further UP/DOWN orders (bit) blocked. If a telegram with the value
“0” is received on the corre-
sponding object, the UP/DOWN orders (bit) are released again.
6.3.6 Block Step/Stop orders (1 Bit)
Default value:
No
Selection options:
No
Yes
Step/stop and turn commands (bit) can be blocked per object (51-54) using this parameter. If a telegram with
the value
“1” is received on the corresponding object during a blinds turn, this turn is carried out up to the
end. Only then further turn commands (bit) are blocked. If a telegram with the value
“0” is received on the
corresponding object, the step/stop or turn commands (bit) are released again.
6.3.7 Block local push button inputs and Somfy RTS orders
Default value:
No
Selection options:
No
Yes
Local push buttons inputs and the Somfy RTS radio signal can be blocked per object (51-54) using this pa-
rameter. If a telegram with the value
“1” is received on the corresponding object during a motor movement,
this turn is carried out up to the end. Only after completion any further commands are blocked which are gen-
erated via local push button inputs or Somfy RTS radio signals. If a telegram with the value
“0” is received on
the corresponding object, the local push button inputs and Somfy RTS radio signals are freed again.
H
This function is deactivated for local push-button inputs if "Yes" has been selected in the "Use universal
binary inputs" menu index card (see section 6.1.4).
6.3.8 Repeat last telegram after security
Default value:
No