animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
44/55
6.12.3
Motor 1…4 Feedback
Default value:
None
Selection options:
Up/Down position
Slat position
Up/Down and slat position
None
•
Up/Down position
Using this parameter the position Up/Down is sent on the bus for the
corresponding motor depending on the parameter “Type of messaging” “0” = upper/”255” = lower.
•
Slat position
With this parameter the slat position is transmitted for the corresponding motor depending on the parameter
“Type of messaging” on the bus. “0/255” = slats opened/”255/0” = slats closed. The value for the position of
the slats which is transmitted over the corresponding object is dependent on the parameter settings on the
menu index ca
rd “General”.
Slats turn Closed/Turned ONLY WITH VENETIAN BLIND.
•
Up/Down and slat position
With this parameter the position Up/Down and the position of the slats for the corresponding motor is trans-
mitted on the bus depending on the parameter “Type of messaging”. “0” = upper/”255” = lower, “0/255” =
slats opened/”255/0” = slats closed. The value for the position of the slats which is transmitted over the cor-
responding object is dependent on the parameter settings on the menu index card
“General”.
Slats turn Closed/Turned ONLY WITH VENETIAN BLIND.
•
None
No positions on the bus are messaged.
6.12.4
Motor 1…4 Type of feedback
Default value:
On demand
Selection options:
On demand
Status change
Cyclic
•
On demand
The current position of the blinds must be requested over object 50.
•
Status change
The current position of the corresponding blind is transmitted after every position change on the bus. The
position is transmitted on the bus when the destination position is reached.
•
Cyclic
This parameter opens a
further parameter (“Every”) with which the time for cyclical sending is set.
value (0%)
value (100%)