animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
34/55
6.6.4 Send starting value on Bus power return
Default value:
No
Selection options:
Yes
No
If this parameter is stopped, the current state of the input is transmitted with the bus voltage return. If this pa-
rameter is set to “No”, the current state of the input is not transmitted.
6.6.5 Contact A and B Cyclic sending of status
Default value:
No cyclic sending
Selection options:
No cyclic sending
On
Off
On and Off
With this parameter it is defined whether the corresponding switch value of the communication object should
be transmitted cyclically.
•
No cyclic sending
The switching value of the communication object is not transmitted cyclically.
•
On
If the object value is “1”, this is transmitted cyclically. If the object value changes by flank change at the local
input or reception of a telegram on “0”, the cyclic sending stops.
•
Off
If the object value is “0”, this is transmitted cyclically. If the object value changes by flank change at the local
input or reception of a telegram on “0”, the cyclic sending stops after “1”.
•
On and Off
If the object value is “1” or “0”, this is transmitted cyclically. If the object value changes by flank change at the
local input or with reception of a telegram, the current object value is transmitted cyclically.
6.6.6 Cyclic sending
Default value:
5 seconds
Selection options:
1
– 3600 seconds
With this parameter the time intervals are defined in which the corresponding object value should be trans-
mitted cyclically.
H
Please beware that cyclical supervision time of the receiver is approximately 4 times higher than that of
the transmitter.