animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
15/55
No. Object name
Type
DPT_ID Description
49
Motor 1-4 Security, high prio
1 bit
1.001
If a telegram with the value
“1” is received on this
communication object, the blinds 1-4 move to the
position parameterized in the ETS parameters
(Security, high prio) and any further move com-
mands will be blocked. With the receiving of a tel-
egram with the value
“0” on this communication
object, the security is turned off and move com-
mands will be accepted again, if the object
44(Security, low prio) has the value “0”. Other-
wise the parameterized action for low security will
be carried out. If
“Repeat last telegram after se-
curity (Yes)
” has been selected in the ETS pa-
rameters and both securities have the value “0”,
the blinds move to the position they were, before
any security was activated.
50
Motor 1-4 Status positions
1 bit
1.001
If a telegram with the value
“1” or “0” is received
on this communication object, the current status
positions of the corresponding blinds are sent to
the bus (objects 73-80).
51
Motor 1 Block functions
1 bit
1.001
If a telegram with the value
“1” is received on one
of these communication objects, the functions pa-
rameterized in the ETS for the corresponding
blind is blocked. If a telegram with the value
“0” is
received on one of these communication objects,
the functions parameterized in the ETS for the
corresponding blind is no longer blocked and
freed again.
52
Motor 2 Block functions
1 bit
1.001
53
Motor 3 Block functions
1 bit
1.001
54
Motor 4 Block functions
1 bit
1.001
55
Motor 1-4 Block functions
1 bit
1.001
If a telegram with the value
“1” is received on this
communication object, the functions parameter-
ized in the ETS for the blinds 1-4 are blocked. If a
telegram with the value
“0” is received on this
communication object, the functions parameter-
ized in the ETS for the blinds 1-4 are no longer
blocked and freed again.
56
Motor 1 Prio automatic/manual
1 bit
1.003
Over these communication objects the priority
automatic function and priority manual function
can be switched. If a telegram with the value
“1”
is received on one of these communication ob-
jects, the automatic functions for the correspond-
ing blind is prioritized activated. If a telegram with
the value
“0” is received on one of these commu-
nication objects, the manual functions for the cor-
responding blind is active.
57
Motor 2 Prio automatic/manual
1 bit
1.003
58
Motor 3 Prio automatic/manual
1 bit
1.003
59
Motor 4 Prio automatic/manual
1 bit
1.003
60
Motor 1 Reset priority
1 bit
1.001
If a telegram with the value
“1” or “0” is received
on one of these communication objects the prior-
ity switching for the corresponding blind is reset.
Automatic functions or manual functions are then
switched to priority active again. Whichever prior-
ity is active depends on the status of the commu-
nication objects 62-65 or whichever priority has
been parameterized in the ETS.
61
Motor 2 Reset priority
1 bit
1.001
62
Motor 3 Reset priority
1 bit
1.001
63
Motor 4 Reset priority
1 bit
1.001
64
Motor 1 IP1 Save/Delete
1 bit
1.002
If a telegram with the value
“1” is received on one
of these communication objects the actual posi-
tion for the corresponding blind is learned as IP1.
If a telegram with the value
“0” is received on one
of these communication objects the IP1 is deleted.
65
Motor 2 IP1 Save/Delete
1 bit
1.002
66
Motor 3 IP1 Save/Delete
1 bit
1.002