animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
42/55
6.11.1.2
Reaction at bus power failure
Default value:
Ignore
Selection options:
Upper end limit
Lower end limit
Ignore
Intermediate position 1 (IP 1)
Intermediate position 2 (IP 2)
Close window
Open window
This parameter defines the position which is moved to with a bus power failure.
6.11.2 Reaction at main power return (230V) (for all motors)
Default value:
Ignore
Selection options:
Upper end limit
Lower end limit
Ignore
Close window
Open window
This parameter defines the position which is moved to with a mains power return (230 V).
6.11.3 Automatic cascading
Default value:
No
Selection options:
No
Yes
If this parameter is set on “Yes”, the motor outputs with one second delay in each case move to the corre-
sponding position. This delay time is taken into account with the start-up of the positions, which are gener-
ated from the settings “Reaction with bus voltage return” and “Reaction with mains voltage return (230 V)”.
H
Advantage: Power spikes can thus be reduced in larger projects.