animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
8/55
Connected to ...
Cabling
Twisted pair
Max. length
Motors
Min.: 4 x 0.75 mm²/18 AWG
Max.: 4 x 2.5 mm²/13 AWG
-
150 m
Push button
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm²/13 AWG
Recommended
100 m
Group control
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 1.5 mm²/15 AWG
Recommended
50 m
KNX Bus
2 x 0.8 mm/20 AWG
Required, corresponding to
KNX topology guidelines
230 V AC
Min.: 3 x 1.5 mm²/15 AWG
Max.: 2 x 2.5 mm²/13 AWG
4 Settings in the delivery state
The Motor Controller KNX can be used in the delivery state also without prior programming by the ETS soft-
ware. Practical presets are implemented in the device. These settings apply to all four motor outputs.
•
Move times UP/DOWN, CLOSED/OPEN = 5 minutes
•
Connection of local conventional push buttons is possible
The local push button inputs are assigned directly to the motor outputs: Push button input 1 controls motor
output 1 (fig. 1). The motor outputs can be controlled through bridging the wire at the push button inputs
when required (fig. 2).
4.1 Function of the Reset/Prog button
H
The basic settings in the KNX Motor Controller can be made using this push button. These basic set-
tings are possible only in the delivery state, before the device with the ETS was programmed, or after the
device was unassigned by the ETS.
The basic settings are overwritten by the settings in the ETS.