6.5.2 Long operation (move) after
Default value:
0.5 seconds
Selection options:
0.3 - 5.0 seconds
This parameter defines the activity time of the corresponding push button which distinguishes between the
sending of a short-term telegram (step/stop) and a long-term telegram (Up/Down). If the time, for example, is
set on 0.5 seconds, a long-term telegram is generated first with a longer pressing of the push button which is
longer than 0.5 seconds. With a shorter activation which is smaller than 0.5 seconds, a short-term telegram
is generated.
6.5.3 Contact type input A
Default value:
Normally open
Selection options:
Normally open
Normally closed
Over this parameter it is defined which type of contact is at the local input A.
Normally open: The contact at the local input is activated closed and not activated opened.
Normally closed: The contact at the local input is activated opened and not activated closed.
6.5.4 Contact type input B
Default value:
Normally open
Selection options:
Normally open
Normally closed
Over this parameter it is defined which type of contact is at the local input B.
Normally open: The contact at the local input is activated closed and not activated opened.
Normally closed: The contact at the local input is activated opened and not activated closed.
6.6
Menu index card “Binary inputs – Switch/Dry contact”
6.6.1 Basic Function
Selected option:
Switch dry contact