4 Prior to assembly
4 Capillary tube sensor of the OTR
5 Contactor
6 Overtemperature reset (OTR)
Overview: Heating element installed
Fig. 2-20_001BE
1 Electric heating element
2 Bracket
3 Heating circuit flow outlet
4 Heating circuit return inlet
5 Vent valve
Mount heating element
►
Mount the bracket and the heating element to the
heat pump as shown.
Fig. 2-21_013BE
Connect the heating element
►
Connect the wires of the heating element to the
contactor
(X2-2)
according to the desired power:
Power 3 kW: Connect wires A1, A2 and A3 to L1, L2
and L3.
Power 6 kW: Connect wires B1, B2 and B3 to L1, L2
and L3.