- 69 -
No.JXC
※
-OMT0007-D
Controller
supply
voltage is
outside set
range.
(01-147)
Over
CrtlVol
D
RESET
SVON
<Contents> The control power supply voltage within the controller is
outside the set range.
<Countermeasure> Make sure that the voltage supplied to the control
power (C24V) of the controller is appropriate.
Caution
If a single power supply is used for both the control power and the
motor power, or the power supply is "inrush-current control type", a
power voltage drop may be caused due to a voltage drop during
acceleration/deceleration.
Current limit
is exceeded
(01-148)
Over load
D
RESET
SVON
<Contents> The output current accumulated value exceeds the specified
value.
<Countermeasure> Make sure there are no obstructions that interfere with
the actuator movement. Also, make sure that the load, speed, acceleration
and deceleration are within the range of the actuator.
The target
position
was not
reached
within the
set time
limit
(01-149)
Posn
failed
ALM
D
RESET
SVON
<Content>
Failed to reach the set position within the set time limit.
<Content>
Make sure there are no obstructions that interfere with
the actuator movement. Also, make sure that the load, speed,
acceleration and deceleration are within the range of the actuator.
Communicati
on error.
(01-150)
Ctrl
Comm
ALM
D
RESET
SVON
<Contents> The connection with the higher-level devices (such as the PC
and teaching box) is disconnected.
<Contents> The connection with the higher-level devices (such as the PC
and teaching box) is disconnected.
In case of the communication failure of PC or teaching box, resetting of
alarm by PC or teaching box is possible after connecting again.
Encoder
error
(01-192)
Encoder
ALM
E
Turn
OFF and
ON the
power
supply for
the
controller
<Contents> Abnormality in communication with the encoder.
<Countermeasure> Check the connection of the actuator cable.
Unable to
find motor
phase in set
time.
(01-193)
Polarity
not found
E
Turn
OFF and
ON the
power
supply for
the
controller
<Contents> Unable to find the motor phase within the set time.
(When the servo motor is turned ON (
“SVON” turns ON) for the first time
after the power is applied, the actuator needs to move a little to find the
motor phase. However, if this actuator movement is prevented, this alarm
will be activated.)
<Countermeasure> Make sure there are no obstructions that interfere with the
actuator movement and then turn ON the servo motor (
“SVON” turns ON).
Output
current limit
is exceeded
set value
(01-194)
Over
current
E
Turn
OFF and
ON the
power
supply for
the
controller
<Contents> The output current of the power circuit is abnormally high.
<Countermeasure> Make sure that there are no short circuits of actuator
cables, connectors, etc.
In addition, make sure that the actuator is compatible with the controller.