- 10 -
No.JXC
※
-OMT0007-D
(6) Supply of power
Supply power 24 VDC.
If the condition is normal, LED on the front of the controller turns ON as shown on the table below.
Items
LED condition
Status
PWR
Green LED is ON
Supply power
ALM
OFF
No alarm
Refer to the
8. LED display (P.
for the explanation of LED lamps.
If the red [ALM] LED on the front of the controller (JXC) is ON, an alarm has been triggered.
Caution
When an alarm is generated
Refer to a corresponding memory of DeviceNet or connect a PC or teaching box to the SI serial I/O
connector and check the details of the alarm. Then, remove the cause of the error referring to the
16. Alarm for Motor Control (P.
Please refer to the manuals of the controller setting software or the teaching box for details of the
alarms.
(7) Setting parameters
It is necessary to set the controller parameters.
The status of the LEDs on the front of the controller matches the table below when the setting of PLC
and parameters complete properly and DeviceNet communication is established.
Items
LED condition
Status
PWR
Green LED is ON
Supply power
ALM
OFF
No alarm
MS
Green LED is ON
Operating normally
NS
Green LED is ON
DeviceNet communications established.
(It has been assigned to the master.)
Refer to
8. LED display (P.
for the explanation of LED lamps.
Communication between PLC and controller is not established when LED[NS] on the front of the
controller(JXC) is OFF, green LED flashes, or red LED flashes or turns ON.
Caution
Communication between PLC and controller is not established.
Refer to
20. Troubleshooting (P.
Check if the communication speed of the PLC and controller and the information of the host computer
are correctly set.