- 53 –
No.JXC
※
-OMY0002
Example:
The initial position: 50mm
↓
Operation of step data No.1: Position: 200mm, Area1-Area2: 150-250mm
↓
Operation of step data No.2: Position: 100mm, Area1-Area2: 130-170mm
(
7
)
Area output
-Procedures- -Timing chart Area output -
●
Operation of Step Data No.1
1) Input step data No. (IN0 to IN5).
↓
2) DRIVE is turned ON.
→ Receive the step data no.1
(From the input IN0 to IN5).
Then, if the DRIVE is turned OFF, the step
data will be output (from the output OUT0
to OUT5).
↓
3) BUSY is turned ON.
(The electric actuator starts the operation).
INP is turned OFF.
↓
4) AREA output is turned ON for the step
data no.1 (at 150mm from the origin
point).
↓
5) BUSY is turned OFF. (The electric actuator stops.)
INP is turned ON.
↓
● Operation of Step Data No.2
6) Input step data No. (IN0 to IN5).
↓
7) DRIVE is turned ON.
→ Receive the step data no.2 (from the input IN0 to IN5).
Then, if the DRIVE is turned OFF, the step data will be output (from the output OUT0 to OUT5).
↓
8) AREA is turned OFF.
BUSY is turned ON. (The electric actuator starts the operation.)
↓
9) AREA output is turned ON for the step data no.2 (at 170mm from the origin point).
↓
10) AREA output is turned
OFF for the step data no.2 (at 130mm from the origin point).
↓
11) BUSY is turned OFF. (The electric actuator stops.)
INP is turned ON.
If the now position is inside of 1
and 2 area scope for step data.
The AREA signal is ON.
Otherwise, the signal is OFF
If the now position is inside of step
data positioning. The INP signal is
ON. Otherwise, the signal is OFF.
IN0~5
DRIVE
OUT0~5
BUSY
INP
AREA
E
lectric actuator
50mm
200mm
100mm
170mm 130mm
Input
Output
150mm
Speed
0mm/s
ON
OFF
・
・
・
・
・
・
・
ON
OFF
・
・