HRX-OM-M005
Chapter 5 Product Operation
HRZD Series
5.3 Operation Screen
5-53
In the event of an error
The ERROR window shown below is displayed when an error occurs that results
in the termination of ongoing circulating fluid recovery. Fluid collection is stopped
accordingly.
Figure 5-83 “Purge Mode Screen”: ERROR Window (E.g.: ALARM)
The lamp stated below comes on corresponding to error type.
Table 5-38 “Purge Mode Screen”: ERROR Window
No.
Item
Descriptions
1 TEMP
OUT
The circulating fluid temperature is out of the range.
(Circulating fluid temperature: Beyond the 10-to-30-°C range)
2 ALARM
COM-01: Water Leak Detect FLT or CH*-07: Reservoir High Level WRN alarm is
raised. The Alarm List screen is displayed when other alarm is raised, and
circulating fluid recovery carries on.
3
TIME OUT
Circulating fluid collection is not completed within the TIME-OUT period.
4
IN RUNNING
The product goes into action.
1
2
3
4
Содержание HRZD020-W1S-W1S
Страница 24: ...HRX OM M005 Chapter 2 Name of Each Section 2 1 Name of Each Section HRZD Series 2 2 ...
Страница 44: ...HRX OM M005 Chapter 4 Product Startup and Shutdown 4 5 Product Startup and Shutdown HRZD Series 4 6 ...
Страница 98: ...HRX OM M005 Chapter 5 Product Operation 5 3 Operation Screen HRZD Series 5 54 ...
Страница 128: ...HRX OM M005 Chapter 8 Appendix 8 8 Thermo Chiller Daily Inspection Sheet HRZD Series 8 20 ...