HRX-OM-M005
Chapter 5 Product Operation
HRZD Series
5.3 Operation Screen
5-7
5.3.4
CH1(2) setting data screen 1, 2
Figure 5-7 “CH1(2) Setting Data Screen 1”
Figure 5-8 “CH1(2) Setting Data Screen 2”
Table 5-6 “CH1(2) Setting Data Screen 1, 2”
No.
Item
Descriptions
Factory
default
1
TEMP SP
Allows the setting of circulating fluid discharge temperature in 0.1°C increments.
20°C
2
FLOW SP
Allows the setting of circulating fluid discharge flow rate in 1L/min increments.
20LPM
3 TEMP
BAND
*1
Allows the selection of the band width for TEMP SP in 0.1°C increments.
1.0°C
4 READY
TIME
Allows the setting of time from when TEMP PV reaches the band range to when
[RDY] is displayed on the Main screen or Ready signal is output, by second.
300 sec
5 HIGH
TEMP
Allows the setting of a temperature that causes “Reservoir High Temp WRN”
alarm, in 1°C increments. An alarm is raised when circulating fluid temperature
exceeds the set temperature.
93°C
6 LOW
FLOW
“Discharge Low Flow WRN” alarm is raised when FLOW PV falls below the set
flow rate. The flow rate setting is allowed in 1L/min increments. Alarm is
disabled if the selection is “0”.
10LPM
-
[SET]
key
Used to display the “Ten-key screen” on page 5-9, which allows numerical input
and setting.
-
-
[Next] key
The CH1(2) setting data screen 1, 2 are alternately displayed. The “CH1(2)
setting data screen 3” on page 5-8 is also displayed if the optional DI control kit
is provided.
-
-
[Return] key
Used to display the “Main screen” on page 5-5.
-
[Tips]
The setting range of items is displayed on the “Ten-key screen” with the
touch of the [SET] key.
*1: See “8.5 BAND/READY Function” in Chapter 8Appendix on page 8-16 for
the TEMP BAND.
1
2
3
4
5
6
Содержание HRZD020-W1S-W1S
Страница 24: ...HRX OM M005 Chapter 2 Name of Each Section 2 1 Name of Each Section HRZD Series 2 2 ...
Страница 44: ...HRX OM M005 Chapter 4 Product Startup and Shutdown 4 5 Product Startup and Shutdown HRZD Series 4 6 ...
Страница 98: ...HRX OM M005 Chapter 5 Product Operation 5 3 Operation Screen HRZD Series 5 54 ...
Страница 128: ...HRX OM M005 Chapter 8 Appendix 8 8 Thermo Chiller Daily Inspection Sheet HRZD Series 8 20 ...