HRX-OM-M005
Chapter 8 Appendix
8.5 BAND/READY Function
HRZD Series
8-16
8.5 BAND/READY
Function
Sets BAND to TEMP SP value, and notifies TEMP PV value reaches within
BAND range by the operation display panel or the communication.
See section 5.3.4 “CH1(2) setting data screen 1, 2” in “Chapter 5 Product
Operation” on page 5-7 for the procedure of the setting.
When the setting is ON
Allows the setting of the BAND and READY TIME. Allows the setting of the
communication output.
Figure 8-7 BAND/READY Function
Examples of Setting
TEMP SP: 20
°
C
BAND: 2
°
C
READY TIME: 60 sec.
・
“RDY” is displayed on the operation touch panel 60 sec. after TEMP PV
value becomes 18
°
C to start output by communication. Necessary condition
is that TEMP PV value after 60-sec. is 20+/-2.0
°
C or less. See section
“5.3.2 Main screen” on page 5-5 for the details of display position.
BAND
TEMP SP
TEMP PV
TEMP READY not display/not output
TEMP READY display/output
READY
TIME