Alarm signal selection
User can designate alarm signal separately for contact signal (OUT1 to OUT6).
See section 5.3.22 “CH1(2)DIO communication setting screen 2” in “Chapter 5
Product Operation” on page 5-33 for signal selecting.
The following table presents the setting-alarm relationship.
Table 8-7 Alarm signal selection
Setting
Alarm
Alarm No.
N/A
Alarm signal remains ON (closed) under normal circumstances.
-
Alarm1
Water Leak Detect FLT
01
Alarm2
*1
-
02
Alarm3
RFGT High Press FLT
03
Alarm4
*1
-
04
Alarm5
Reservoir Low Level FLT
05
Alarm6
Reservoir Low Level WRN
06
Alarm7
Reservoir High Level WRN
07
Alarm8
Temp. Fuse Cutout FLT
08
Alarm9
Reservoir High Temp. FLT
09
Alarm10
*1
-
10
Alarm11
Reservoir High Temp. WRN
11
Alarm12
Discharge Low Flow FLT
12
Alarm13
Discharge Low Flow WRN
13
Alarm14
Heater Breaker Trip FLT
14
Alarm15
Pump Breaker Trip FLT
15
Alarm16
CPRSR Breaker Trip FLT
16
Alarm17
Interlock Fuse Cutout FLT
17
Alarm18
*2
DC Fuse Cutout WRN
18
Alarm19
FAN Motor Stop WRN
19
Alarm20
Internal Pump Time Out WRN
20
Alarm21
Controller Error FLT
21
Alarm22
Memory Data Error FLT
22
Alarm23
Communication Error WRN
23
Alarm24
*2
DI Low Level WRN
24
Alarm25
Pump Inverter Error FLT
25
Alarm26
*1
-
26
Alarm27
*1
-
27
Alarm28
CPRSR Inverter Error FLT
28
Alarm29 -
29
Alarm30 -
30
Alarm31 -
31
Alarm32 -
32
●
Example
With parameter “OUT” on the Initial Setting screen set to “Alarm1”, alarm “Water Leak Detect FLT” is
detected, the alarm contact signal is switched to OFF (open).
*1: Alarms 2, 10, 26, 27, and 29 to 32 are assigned with no alarm. The alarm signal remains ON (closed)
despite Alarm10 being specified.
*2: Alarms 18 and 24 are alarms indicating accessories (optional).
Содержание HRZD020-W1S-W1S
Страница 24: ...HRX OM M005 Chapter 2 Name of Each Section 2 1 Name of Each Section HRZD Series 2 2 ...
Страница 44: ...HRX OM M005 Chapter 4 Product Startup and Shutdown 4 5 Product Startup and Shutdown HRZD Series 4 6 ...
Страница 98: ...HRX OM M005 Chapter 5 Product Operation 5 3 Operation Screen HRZD Series 5 54 ...
Страница 128: ...HRX OM M005 Chapter 8 Appendix 8 8 Thermo Chiller Daily Inspection Sheet HRZD Series 8 20 ...