HRX-OM-M005
Chapter 8 Appendix
8.4 Offset Function
HRZD Series
8-14
8.4.1
Example of offset function
When the discharge temperature of the circulating fluid is at 30°C, heat is
dissipated by 1°C so the circulating fluid in your system to be 29°C. Under the
above condition, the following process is to be performed with the utilization of
MODEs 1 to 3.
Figure 8-3 Example of Offset Function
When MODE1 is selected
This mode enables this product to exercise temperature control to obtain 31°C
(TEMP SP value +OFFSET value), with OFFSET value set at 1°C. Once the
discharge temperature of the circulating fluid becomes 31°C, 1°C-thermal
dissipation occurs to allow the circulating fluid in your system to be 30°C. TEMP
SP value is obtained for your system.
Note that “31°C” is recorded in TEMP PV and communication data.
Figure 8-4 When MODE1 is selected
Heat dissipation:
1
℃
This system
Your system
Discharge temp.:
30
℃
Circulating fluid temp. in your
system: 29
℃
TEMP PV 30
℃
TEMP SP 30
℃
External communication
Communication data
TEMP PV 30
℃
Heat dissipation:
1
℃
This system
Your system
Discharge temp.:
31
℃
Circulating fluid temp. in your
system: 30
℃
TEMP PV 31
℃
TEMP SP 30
℃
OFFSET 1
℃
External communication
Communication data
TEMP PV 31
℃
TEMP PV
31
℃
Содержание HRZD020-W1S-W1S
Страница 24: ...HRX OM M005 Chapter 2 Name of Each Section 2 1 Name of Each Section HRZD Series 2 2 ...
Страница 44: ...HRX OM M005 Chapter 4 Product Startup and Shutdown 4 5 Product Startup and Shutdown HRZD Series 4 6 ...
Страница 98: ...HRX OM M005 Chapter 5 Product Operation 5 3 Operation Screen HRZD Series 5 54 ...
Страница 128: ...HRX OM M005 Chapter 8 Appendix 8 8 Thermo Chiller Daily Inspection Sheet HRZD Series 8 20 ...